The complete system specification sets out the requirements for the Western Colloid SM-1P-14-3G-A fluid applied reinforced roof system. It recovers a smooth surface or cap sheet with one ply of polyester and glass fiber roving, finished with an aluminum reflective surface. The five-page PDF is revised 10/20.
Part 1 lists the applicable ASTM, UL and Western Colloid detail publications, the pre-roofing conference, a two-year contractor warranty, and the manufacturer’s application instructions and data sheets. The environmental conditions set a minimum application temperature of 55°F and rising, and state that application is not permitted while ice or frost is on the roof deck.
The system components table lists a base coat of #298 emulsion at 5 gallons and 19 lb, one ply of polyester fabric at 2.5 lb, a top coat of #298 emulsion at 9 gallons and 35 lb, 3 lb of chopped glass roving, and 1.5 gallons of SilverWhite aluminum at 4.5 lb. The dry total is 64.0 lb per 100 square feet at about 124 mils. Part 2 lists the U.L. Class A criteria and names All Weather Elastic Cement #8000 as a sealant for wet repairs and metal flanges.