CF Tuff Wall®
- Manufacturer
- Metl-Span
- Product
- CF Tuff Wall®
- Status
- Current
- Market
- United States
- Last verified
- September 20, 2026
Overview
CF Tuff Wall is a stucco-like insulated metal wall panel from Metl-Span with a polyisocyanurate (PIR) foam core. The exterior surface is a hard aggregated, fiber-reinforced polymer coating applied in the factory as the Tuff Cote finish system. It is a concealed-fastener panel used on commercial and industrial buildings in the United States.
The coating resists impact and abrasion. The exterior finish carries a 10-year limited warranty. The panel is a member of the insulated metal wall panels range, where it is the textured, coated option.
Dimensions
- Width: 36 in. or 42 in.
- Thickness: 2 in., 2-1/2 in., 3 in., 4 in., 5 in. or 6 in.
- Length: 8'-0" to 32'-0" installed horizontally; 8'-0" to 40'-0" installed vertically
Data sheets and technical documents
Current product files and retained historical revisions.
Current files
Archived files
No older reviewed revisions are archived for this product yet.
Faces and profile
The exterior face is stucco-embossed G-90 galvanized and/or AZ-50 aluminum-zinc coated steel in 24 or 22 gauge, with the Tuff Cote finish system applied at the factory. Panels 2, 2-1/2, 3 and 4 in. thick have no exterior profile. Panels 5 and 6 in. thick have a Mesa profile nominally 1/8 in. deep.
The interior face is stucco-embossed G-90 galvanized and/or AZ-50 coated steel in 26, 24 or 22 gauge, with a Light Mesa profile nominally 1/16 in. deep.
Finishes
- Exterior texture: Tuff Cote finish system
- Finish options recorded: Applied Finishes and Igloo White
- Metallic finishes can show color shift, shade variance, striations and longitudinal patterning
- Light Stone in the Tuff Cote system does not match Light Stone in the Standard SP offering
Core and joint
The core is foamed-in-place PIR foam, a zero ozone depletion potential Class 1 foam. The joint is an offset double tongue-and-groove with an extended metal shelf for positive face fastening. Concealed clips eliminate thermal short circuits.
Thermal values
The k-factor is 0.112 at 35°F (1.6°C), based on ASTM C518, ASTM C1363 and thermal modeling. Values below are for a 42 in. width at 35°F.
- 2 in.: U-factor 0.058, R-value 17.9
- 2-1/2 in.: U-factor 0.045, R-value 22.4
- 3 in.: U-factor 0.038, R-value 26.9
- 4 in.: U-factor 0.028, R-value 35.9
- 5 in.: U-factor 0.022, R-value 44.8
- 6 in.: U-factor 0.019, R-value 53.8
Fire testing and approvals
- ASTM E84: flame spread under 25, smoke developed under 450
- ASTM E119: one hour non-load bearing rating with two layers of Type X gypsum, vertical or horizontal installation
- FM 4880: Class 1 fire rating, product approved; an exterior wall requires FM 4881 approval
- NFPA 285-19: the panel assembly met the requirements of the standard
- NFPA 286: the specimen met the criteria of IBC Section 803.1.2.1
- CAN/ULC S101: one hour non-load bearing rating with two layers of Type X gypsum, and the 10 minute stay-in-place requirement
- CAN/ULC S102, S134 and S138: met the requirements of each standard
Structural, air and water performance
- ASTM E72: results in a load chart
- FM 4881: Class 1 exterior wall structural performance, with a VSH rating in the FM Approval listings
- ASTM E283: air infiltration under 0.04 cfm/ft² at 1.57 psf
- ASTM E2357: under 0.04 cfm/ft² at 1.57 psf after 2,000 cycles at +/- 16.71 psf, with and without penetrations
- ASTM E331: no uncontrolled leakage at 6.24 psf for 2 hours
State of Florida product approval is held; the approval does not include the High Velocity Hurricane Zone.
Details and specifications
- Specification section: MasterFormat 2012 Section 07 42 13.19
- Load span tables are based on Allowable Stress Design (ASD)
- Thermal values are based on ASTM C518, ASTM C1363 and thermal modeling
The V6 X-Span Clip is the listed concealed clip, with an edge trim detail F5986.
- Base: H-BE-01 extended trim leg, H-BE-02 overhang with drip edge, H-EB-01 flush extruded base
- Corners: H-CE-01 outside, H-CE-02 inside, H-CE-03 formed, H-CE-04 trimless inside, H-EC-01 extruded outside
- Eave, parapet and soffit: H-BE-03 wall and soffit
- Header, jamb and sill: H-EW-01, H-EW-02, H-EW-03, H-WH-01, H-WJ-01, H-WS-01
- Joints: H-JT-01 and H-JT-02 side joint, H-VJ-01 vertical joint with gasket, H-VJ-02 vertical joint with wet seal
- Vertical: C&I CF Vertical Detail Book, in PDF and CAD